Rosemount 8800C Vortex Flowmeter

Rosemount 8800D Vortex Flowmeter

 Rosemount Reliability -The 8800D Vortex eliminates impulse lines, ports, and gaskets to
improve reliability.

• Non-clog Design - Unique gasket-free construction which has no ports that can clog.


• Vibration Immunity - Mass Balancing of the sensor system, and Patented Adaptive Digital
Signal Processing (ADSP) provide Vibration immunity.


• Replaceable Sensor - The sensor is isolated from the process and can be replaced without
breaking the process seals. All line sizes use the same sensor design allowing a single
spare to serve every meter.

• Simplified Troubleshooting - Device Diagnostics enable field verification of Meter
Electronics and Sensor with no process shutdown

 

 

The 8800D is available in wafer style meterbodies for 1/2 through 8 inch line sizes, and
ASME B16.5 (ANSI), DIN, or JIS flanged style meter bodies for 1/2 through 12 inch line sizes.
• Alignment rings, provided with each wafer-style flowmeter, ensure that the meter
body is properly centered with the adjacent    piping.


• Both wafer and flanged style meter bodies are available in 316L stainless steel and Nickel
Alloy materials of construction.  

 

                 
• Available up to ANSI class 1500 for 1 through 8 inch (25 mm through 200 mm) and ANSI
class 900 for 1/2 inch (15 mm) through 8 inches(200 mm).

 

Analog Output Adjustment
Engineering units and lower and upper range values are
user-selected. Output is automatically scaled to provide 4 mA at
the selected lower range value, 20 mA at the selected upper range
value. No frequency input is required to adjust the range values.
Scalable Frequency Adjustment
Value of one pulse can be set to equal desired volume in selected
engineering units.
Ambient Temperature Limits
Operating
–58 to 185 °F (–50 to 85 °C)
–4 to 185 °F (–20 to 85 °C) for flowmeters with local indicator
Storage
–58 to 250 °F (–50 to 121 °C)
–50 to 185 °F (–46 to 85 °C) for flowmeters with local indicator
Pressure Limits
Flange Style Meter
Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and
1500, DIN PN 10, 16, 25, 40, 64, 100, and 160, and JIS 10K,
20K, and 40K
Reducer Style Meter
Rated for ASME B16.5 (ANSI) Class 150, 300, 600, and 900,
DIN PN 10, 16, 25, 40, 64, 100, and 160.
Dual Sensor Style Meter
Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and
1500, DIN PN 10, 16, 25, 40, 64, 100, and 160, and JIS 10K,
20K, and 40K
Wafer Style Meter
Rated for ASME B16.5 (ANSI) Class 150, 300, and 600, DIN
PN 10, 16, 25, 40, 64, and 100, and JIS 10K, 20K, and 40K