EJA118W Diaphragm SeaLED Differential Pressure Transmitters

EJA118W Diaphragm Sealed Differential Pressure Transmitters Features : Diaphragm seals are used to prevent process medium form entering directly into the pressure-sensing assembly of the differential pressure transmitter, they are connected to the transmitter using capillaries filled with fill...

Send Inquiry
EJA118W Diaphragm SeaLED Differential Pressure Transmitters

 EJA118W Diaphragm Sealed Differential Pressure Transmitters

Features :

Diaphragm seals are used to prevent process medium form entering directly into the pressure-sensing

assembly of the differential pressure transmitter, they are connected to the transmitter using capillaries

 filled with fill fluid.

 

Standard Specifications :

 

Measurement Ranges:


Capsule       Measurement Span      Measurement Range

 

M               2.5 to 100 kPa                  -100 to 100 kPa
                                                          {-10000 to 10000 mmH2O}
                 {250 to 10000 mmH2O}


H              25 to 500 kPa                           -500 to 500 kPa
                                                               {-5 to 5 kgf/cm2}
                {0.25 to 5 kgf/cm2}

 

Output Signal “”:
4 to 20 mA DC, 2-wire system with digital communication

 

Failure Alarm:
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more(standard)
Down-scale: -5%, 3.2 mA DC or less
-2.5%, 3.6 mA DC or less (Optional code /F1)
Note: Applicable for Output signal code D and E

 

Supply Voltage “”:
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional code /A)
10.5 to 30 V DC for intrinsically safe, Type n, nonincendive,
or non-sparking type
10.5 to 28 V DC for TIIS intrinsically safe type

 

Conditions of Communication Line “”:
Power supply voltage;
16.4 to 42 V DC
Load resistance; See Figure 1.
Note: In case of an intrinsically safe transmitter, external
load resistance includes safety barrier resistance.


Communication distance;
2 km, when CEV polyethylene-insulated
PVC-sheathed control cables are used.
Note: Communication distance varies depends on kind of
cable.


Load capacitance; 0.22 µF of less.
Load inductance; 3.3 mH or less.
Spacing from power line; 15 cm or more.
Input impedance of receiver connected receiving resistance;
10 k or more at 2.4 kHz
(See Optional Specifications for Intrinsically safe type)

 